PCC Auto On-off Grid Switching Cabinet

Seamless and reliable automatic transfer between grid and off-grid operation.

BOS
Key features
  • Rated Power: 75kVA; 125kVA; 250kVA; 375kVA
Technical specifications
ModelsModel AModel BModel CModel D
Basic ParametersRated Power75 kVA125 kVA250 kVA375 kVA
Wiring MethodThree-phase Four-wire + PE (3P4W+PE)
Rated Grid VoltageAC 400 V
Voltage RangeAC 400 V ±15%
Rated Frequency50 / 60 Hz
Frequency Range50 / 60 Hz (±2.5 Hz)
Long-term Overload Capability110%
Off-grid → On-grid Switching Time13–24 ms
On-grid → Off-grid Switching Time25–42 ms
Rated Output Current33–58 A
Rated Input Current40–65 A
Max. Efficiency99%
Auto-protectionGrid-side overvoltage, Undervoltage, Overfrequency, Underfrequency, Overtemperature, Emergency stop and Output overload protection
General ParametersIsolation TransformerYES
Protection LevelIP54
Cooling MethodForced Air Cooling
Anti-corrosion GradeC3
Operating Temperature–30°C ~ 50°C
Relative Humidity0–95% (Non-condensing)
Operating Altitude< 3000 m
Noise Emission≤75 dB
Size( L*W*H)900×850×2100 mm1000×1000×2100 mm
Max. WeightAbout 1000 kgAbout 1600 kg
Number of grid inputs1
Number of PCS inputs1
Number of load inputs1
Communication interface1 × RS485, 1 × CAN
Communication ProtocolModbus RTU, CAN2.0B
Notice• The system will be derated when ambient temperature exceeds 45°C. • The system will be derated when altitude exceeds 3000 m.

The above technical specifications are typical values. Final configuration and parameters are subject to contract or technical agreement.